01 Loft conversions and escape
A loft conversion turns a roof space into a room where people sleep, and the fire rules follow. In Approved Document B, para 2.2 draws the line at 4.5 m above ground: up to it, an escape window can serve the storey. Para 2.10 sets that window at "A minimum area of 0.33m2.", "A minimum height of 450mm and a minimum width of 450mm", and the openable area's lower edge no higher than "a maximum of 1100mm above the floor". Past the line, para 2.5 starts from "Where a new storey is added through conversion to create a storey above 4.5m" and offers a protected stairway or an alternative escape route.
Para 2.23 permits sprinklers in the open-plan areas as an alternative. The Building Regulations route is settled before work starts. Central Bedfordshire Council's building control team is on 0300 300 8635 (building control, not planning). A registered building control approver is the other path: where the council signs off with a completion certificate, an approver signs off with a final certificate. The roof that stays must also meet Part L: Table 4.3 gives 0.35 as the threshold and 0.16 as the improved figure for a retained roof. A loft hatch too small for a stair, or a pitch too shallow for headroom, is worth knowing about before a design is drawn.